Elecquip
Home > Product Catalog > Cable Glands > Cable Glands > ICG 653/T Cable Gland

CABLE GLANDS


Enlarge image

ICG 653/T Cable Gland



Enlarge image
For clamping pliable wire armour. No cold-flow ore soft inner sheath. Fully inspectable armour clamping. Dual certification EExd Flameproof and EExe Increased Safety. Wide cable acceptance range eases selection. Same hexagon size enables faster installation.

APPLICATION
Outdoor or indoor. For use with pliable wire armoured 'T' elastomer and plastic insulated cable, with extruded or taped bedding, e.g. soft sheathed fire-retardant cable. In particular with:- a) Cables not complying with BS 5308, BS 5467, BS 6116, BS 6346, BS 6883 or equivalent. b) Enclosures containing an ignition source in gas group II areas. c) Enclosures exceeding 2 litres in volume and containing an ignition source installed in a Zone 1 area. FUNCTION: Provides armour clamping. Provides a compound seal aourund individual cable cores. Provides a seal on outer sheath of cable.


DETAILS
The purpose of this type of gland is to form a barrier between the individual insulated conductors within the cable, and prevent entry into the cable of the products of an explosion within the enclosure. This gland provides an effective inner seal on cables having tape bedding or 'soft' sheaths as in some types of fire-retardent cables. The seal of a conventional gland for the cable inner sheath is replaced with a single compound filled cahmber which permits packing around individual insulated conductors. Assembly of the gland comresses the packing material and distributes the comound evenly to effect a barrier at point of entry into enclosure. Sealing on outer sheath of cable and armour clamping are provided in the conventional manner.


CERTIFICATION AND APPROVAL
BASEEFA Certificate No. Ex 85B1258U. EExd. EN 50014, EN 50018 and EN 50019. Suitable for use in Zone 1 and 2. Suitable for use in Group II A, II B and II C. Meets the requirements of IP 66. OPERATING TEMPERATURE RANGE: -60C to +100 degrees C.


MATERIALS AND FINISHES
Hawke glands are manufactured as standard in brass (BS. 2874). Alternative materials include stainless steel (BS. 970) and mild steel (BS. 970). Hawke glands can be supplied plated to suit the customers application, e.g. zinc, nickel etc.


  Cable Glands
ICG 653/UNIV Universal Cable Gland
501/453 UNIV Universal Cable Gland
ICG 653/T Cable Gland
501/453/RAC 353/RAC Cable Glands
N501/453/T Cable Gland
VBL 453/RAC VBL 353/RAC Cable Glands
501/452/RAC 352/RAC Cable Glands
A501/421 Cable Glands
153/RAC Cable Gland
N153/T Cable Gland
VBL/153/RAC Cable Gland
MAGNUM Gland Range
N300 Plastic Cable Glands

  QUOTATION ITEMS

View Quotation

 

Add To QuoteGland Ref. SizeEntry Thread Size (Metric)Inner Sheath/Cores 'U'Standard Seal 'O' (Min.)Standard Seal 'O' (Max.)SOS Seal 'O' (Min.)SOS Seal 'O' (Max.)'P''R' Pliable Wire ArmourHexagon Across FlatsHexagon Across Corners
AddOT20.010.010.516.07.012.5547/0.4524.027.7
AddAT20.012.312.920.911.915.6547/0.4530.034.6
AddBT25.018.217.027.216.021.3577/0.4536.041.6
AddCT32.024.525.033.621.027.6607/0.4546.053.1
AddC2T40.029.533.043.028.034.0667/0.7155.063.5
AddCT50.041.538.552.633.041.0737/0.7165.075.1
AddET63.053.352.065.346.054.9737/0.9 7/1.2580.092.4
AddFT75.066.064.078.057.067.0747/0.9 7/1.2595.0109.6