CABLE GLANDS
|
 |
Enlarge image
|
 |
VBL 453/RAC VBL 353/RAC Cable Glands
|
 |
 |
 |
Reduces stocking requirements, one armour clamp ring suits W/X/Y/Z armour. Nine sizes suita cable outer diameters up to 78mm. Fully inspectable armour clamping. Provides seal on lead sheath cable. Wide cable acceptance range eases selection. Same hexagon size enables faster installation.
APPLICATION; Outdoor or Indoor. For use with lead sheathed, single wire armoured 'W', wire braided 'X', aluminium strip armoured 'Y', steel tape armoured 'Z' and non-armoured (A40 elastomer, plastic and paper insulated cable. NOTE: When using this type of gland with non armoured cable the armour clamping components are still required for compression of inner seals. FUNCTION: Procides armour clampng, using one component for all armour braid types W, X, Y, Z. Provides a seal and electrical bond on lead inner sheath of cable. Provides a seal on outer sheath of cable.
VBL 453 / RAC CERTIFICATION AND APPROVAL : BASEEFA Certificate No. 1016U. Exd II C BS4683: Part 2. Suitable for use in Zone 1 and Zone 2. Suitable for Group II A, II B, and II C. Meets the requirements of IP66.
VBL 353 / RAC CERTIFICATION AND APPROVAL : BASEEFA Certificate No. Ex 813165U. EExe II. EN 50014 and En 50019. Suitable for use in Zone 1 and Zone 2. Suitable for Group II A, II B, and II C. Meets the requirements of IP66.
OPERATING TEMPERATURE RANGE -20C to+80 degrees C. MATERIALS AND FINISHES: Hawke glands are manufactured as standard in brass (BS. 2874). Alternative materials include stainless steel (BS. 970) and mild steel (BS. 970). Hawke glands can be supplied plated to suit the customers application, e.g. zinc, nickel etc.
|
 |
|
|
 |
|